RH-2-I MR
Relative Humidity
Transmitters
The RH-2 and RHT-2 are designed for continuous
monitoring of relative humidity (RH) or relative humidity and temperature
(RHT). The units feature very low profile sensor enclosures that are
virtually unnoticeable in most installations.
The RH-2-I-MR Series
is available with ±2% RH accuracy (20% to 95% RH). For monitoring and
controlling in critical environments, the units can be precision
calibrated to 1% accuracy within a specified RH range.
The RH and
RHT transmitters provide a linear output of 4-20mA corresponding to 0 to
100% RH. The RHT transmitter also provides a 4-20mA signal corresponding
to any of the selected standard temperature ranges specified.
The
relative humidity and temperature sensors are housed in heavy duty,
compact, locking enclosures. Enclosures may be removed and painted, which
further helps blend them into any environment. The sensor enclosure is
remotely mounted up to 50 feet from the transmitter.
The RH sensor
incorporates a bulk polymer resistive element. The polymer is impervious
to most contaminants and, since it is a bulk resistive device, surface
contamination such as dust will not alter the accuracy of the readings.
Imbedded in the polymer is an interdigitated grid which sense resistance
change as the polymer absorbs or emits molecules of water.
Mounted
remotely, the electronics are contained in a rugged pressure-cast aluminum
weatherproof housing designed for maximum protection. Continuous
temperature compensation adjusts for temperature-induced change in the RH
sensor output. The compensation provides high measurement accuracy over
the entire operating range of the instrument.
Features
 |
Low Profile |
 |
Compact Sensor Enclosure |
 |
Replaceable, Plug-in Bulk Polymer Resistance RH
Sensor |
 |
Resistant to Contamination |
 |
Temperature Compensation |
|
|
SPECIFICATIONS
Humidity:
Sensing
Element: Resistance
change of bulk polymer sensor. Accuracy
at 77°F (25ºC): +/- 2% RH. 20-95%
RH including hysteresis, linearity, and repeatability. Temperature Effect:
Less than 0.06% per ºF (Less than 0.11% per
ºC) Sensitivity: 0.1% RH Repeatability:
0.5% RH. Linearity: See
Accuracy. Hysteresis: Lessthan 1% Sensor
Interchangeability: ±3% nominal
Operating Range: RH
Sensor: 0% to 99% RH,
non-condensing, -40º to +170ºF (-40º to 76ºC) Electronics: 0% to
95% RH, non-condensing, -40º to 54ºC (-40º to +130ºF) Max. Air
Velocity: 10,000
ft/min Output Ranges:
4-20mA current, 2-wire, isolated,
loop-powered for 0-100%, RH (standard) into 0-900
ohms
Long Term Stability: Less than 1% drift per year typical Supply
Voltage: 12-36
VDC Storage
Temperature: -65º to +70º (-85º to
+158º).
Temperature:
Sensing Element: Platinum RTD, 4 wire measurement. Accuracy at 25º C: +/-
0.3º (+/- 0.5º). Temperature effect:
Less than 0.02% per ºC
(0.01%ºF) Sensitivity:
0.1% RH Repeatability: 0.1% RH Linearity:
Better than 0.1% Hysteresis: Less
than 0.01% Sensor Interchangeability:
±0.3ºC (±0.5ºF) Output Ranges: 4-20mA,
2-wire, isolated, loop powered. Standard: -29ºC to +60ºC (-20ºF to
140ºF) Long-term Stability:
Less than 1ºF drift per year
typical.
Applications
 |
Museums |
 |
Archives |
 |
Executive Offices |
 |
High Profile Areas |
|